Equipment Grounding Conductor Calculator — NEC-Compliant Sizing

Equipment Grounding Conductor Calculator

Calculate proper equipment grounding conductor (EGC) sizes for electrical systems per NEC requirements. Get accurate sizing for safety and compliance.

Step 1: Circuit Details

NEC Requirements

Equipment grounding conductors must be sized per NEC Table 250.122 based on the overcurrent device rating. Minimum size is 14 AWG for copper.

Step 2: Installation Details

Grounding Conductor Purpose

The equipment grounding conductor provides a low-impedance path for fault current, enabling overcurrent devices to operate and clear ground faults.

Equipment Grounding Conductor Calculation Results

Summary
Conductor Sizes
NEC Compliance

Required Grounding Conductor Size

10 AWG
For 60A Circuit – Copper
Circuit Amperage
60 A
Conductor Material
Copper
NEC Table Reference
250.122
Safety Margin
10%

Grounding Conductor Size Options

Minimum NEC Size
10 AWG
NEC Table 250.122
Recommended Size
10 AWG
With Safety Factor
Aluminum Equivalent
8 AWG
If using Aluminum
Next Standard Size
8 AWG
For Future Expansion

Sizing Rules

Equipment grounding conductors sized per NEC Table 250.122 must not be smaller than shown. If conductors are increased in size, the EGC must be increased proportionally.

NEC Compliance & Standards

NEC Table 250.122 Reference

Equipment Grounding Conductor Sizing

Table 250.122 specifies minimum size equipment grounding conductors for grounding raceways and equipment based on the rating or setting of automatic overcurrent devices.

Rating of Overcurrent Device (Amps) Copper (AWG or kcmil) Aluminum (AWG or kcmil)
15 14 12
20 12 10
30-60 10 8
70-100 8 6
110-200 6 4