Cable Length Calculator — Calculate Wire & Cable Requirements

Cable Length Calculator

Calculate cable length requirements, voltage drop, and wire gauge for electrical installations. Determine proper cable sizing for optimal performance and safety.

Step 1: Electrical Parameters

120 V
15 A
100 ft

Voltage Drop Formula

VD = (2 × L × R × I) / 1000
Where L = Length, R = Resistance, I = Current

Step 2: Cable Specifications

Common Cable Applications

14 AWG: Lighting circuits (15A max)
12 AWG: General outlets (20A max)
10 AWG: Kitchen appliances (30A max)
8 AWG: HVAC systems (40A max)

Cable Calculation Results

Summary
Wire Gauge Comparison
Formula & Standards

Recommended Wire Gauge

12 AWG
Voltage Drop: 3.2% • Max Length: 156 ft
Voltage Drop
3.8 V
Voltage Drop %
3.2%
Power Loss
57 W
Max Recommended Length
156 ft

Wire Gauge Comparison

Wire Gauge (AWG) Max Current (A) Resistance (Ω/1000ft) Max Length (ft) at 120V/15A

Voltage Drop Formula & Standards

Voltage Drop = (2 × Length × Resistance × Current) / 1000

Where:
• Length = One-way length of cable (feet)
• Resistance = Resistance per 1000ft for the wire gauge (Ω)
• Current = Load current in amps (A)
• 2 = Factor for single-phase (round trip)

For three-phase systems:
• Voltage Drop = (√3 × Length × Resistance × Current) / 1000

Standards:
• NEC recommends max 3% voltage drop for branch circuits
• Max 5% voltage drop for feeder and branch circuits combined

Example Calculation

Example: 120V, 15A, 100ft with 12 AWG Copper

Resistance of 12 AWG copper: 1.588 Ω/1000ft
Voltage Drop Calculation:
VD = (2 × 100 × 1.588 × 15) / 1000 =
(2 × 100 × 23.82) / 1000 =
4764 / 1000 = 4.764V

Percentage Voltage Drop:
(4.764V / 120V) × 100 = 3.97%

Power Loss:
Power Loss = Voltage Drop × Current = 4.764V × 15A = 71.46W